Application:
The earth leakage circuit breaker type FIN is in conformity with the standards of VDE 0664,CEE 27 and BS 4293. It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line.Thus it is suitable to avoid the shock hazard and fire caused by earth leakage. FIN ELCB is mainly suitable for use in varieties of plants and enterprises,building,construction,commerce,guesthouses and families.It can be used in circuits up to single phase 240V,three phases 415V,50 to 60Hz.
Technical Specification:
Type | FIN25 | FIN40 | FIN63 |
Rated current I△n (A) | 20 | 40 | 63 |
Rated operating current for earth leakage I△n (A) |
0.03,0.1,0.3,0.5 | ||
Rated non-operating current for earth leakage I△n (A) |
0.51 I△n | ||
Voltage Un (V) | 240(220)/415(380) | ||
Pole | 2 | 3 | 4 |
Technical data
Operating time (second) | I△n | 2I△n | 0.25A(or 5I△n) |
0.2 | 0.1 | 0.04 | |
Limited value of non-operating current for balance load or unbalance load | 2In | ||
In min value of rated making and breaking capacity | In=25 | In=40 | In=63 |
200 | 300 | 400 | |
Rated conditional short circuit Inc (A) | 1500 | 2000 | 3000 |
Endurance (times) | 4000 |