Home | Sitemap

Wenzhou Aolang Import & Export Co.,Ltd

E-mail: electric@aolangco.com

Current Location: xabond >> Products >> Low Tension Electric ... >> MCCB >> ODPX series MCCB

ODPX series MCCB
ODPX 125 3P ODPX 160 3P
ODPX 250 3P ODPX 630 3P
Application
ODPX series MCCB is applicable circuit of AC 50/60Hz, rated current 25-250A, for distribute energy of electricity & infrequent making & breaking circuit in normal conditions. The products conforms to IEC60947-2.
Specifications
Type   ODPX 125 ODPX 160 ODPX 250
ODPX-E ODPX ODPX ODPX ODPX-E ODPX
3-4 3-4
Pole number 16-125 25-250
Rated current In(A)
The electrical characteristic satisfies
             
EN60947-2
Rated working voltage
    500     690  
Ue(50-60Hz)     250     250  
Rated working voltage Ue=(V)     500     690  
Rated insulation voltage Ui~(V)     6     8  
Rated impulse voltage Uimp(KV)     A     A  
Usage group   E       H L
Moulded case switch type 230/ 40V~ 22 35 50 60 100 170
Limited breaking 400/415V~ 16 25 36 36 70 100
capacity(KA) 440V~ 10 18 20 30 60 70
  480/500V~ 8 12 14 25 40 40
  600V - - - 20 25 25
  690V - - - 16 20 20
250V~ 16 25 30 36 40 40
    100 50 50 100 75 50
    32 52.5 75.6 75.6 154 220
Short-circuit closed capacity(400V~)              
Short-time withstand current Icw(KA) mechanical 7000     7000  
Life (open, close for a time) Electrical 1000     1000  
Insulation capacity              
Dimension and weight 3 pole 75.6×120×74 105×200×105
Dimension 4 pole 101×120×74 140×200×105
(L×W×H)(mm) 3 pole 1 2.5
Weight(kg) 4 pole 1.2 3.7