GV series Motor Protection Circuit Breaker
GV2-M GV2-ME & AU AX AS GV2-RS & AE
AN GV3-M GV3-ME
Application
GV series motor protection circuit breakers are mainly used for the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full-voltage starter to start and cut off the motor, under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.
Specifications
Type Rated standard power of 3-phase
motors 50/60Hz in category AC-3
Setting range
(A)
220V 380V 415V 440V 500V 660V
KW KW KW KW KW KW
GV2-M01 /ME -- -- -- -- -- -- 0.1-0.16
GV2-M02 /ME -- -- -- -- -- -- 0.16-0.25
GV2-M03 /ME -- -- -- -- -- -- 0.25-0.4
GV2-M04 /ME -- -- -- -- -- 0.37 0.4-0.63
GV2-M05 /ME -- -- -- 0.37 0.37 0.55 0.63-1
GV2-M06 /ME -- 0.37 -- 0.55 0.75 1.1 1-1.6
GV2-M07 /ME 0.37
0.75
0.75
1.1
1.1
1.5
1.6-2.5
GV2-M08 /ME 0.75
1.5
1.5
1.5
2.2
3
2.5-4
GV2-M10 /ME 1.1
2.2
2.2
3
3.7
4
4-6.3
GV2-M14 /ME 2.2
4.
4
4
5.5
7.5
6-10
GV2-M16 /ME 3
5.5
5.5
7.5
7.5
9
9-14
GV2-M20 /ME 4
7.5
9
9
9.
11
13-18
GV2-M21 /ME 5.5
11
11
11
11
15
17-23
GV2-M22 /ME 5.5
11
11
11
15
18.5
20-25
GV2-M32 /ME 7.5
15
15
15
18.5
26
24-32
GV3-M06 /ME --
0.37
-- 0.55
0.75
1.1
1-1.6
GV3-M07 /ME 0.37
0.75
1.1
1.1
1.1
1.5
1.6-2.5
GV3-M08 /ME 0.75
1.5
1.5
1.5
2.2
3
2.5-4
GV3-M10 /ME 1.1
2.2
2.2
3
3.7
4
4-6
GV3-M14 /ME 2.2
4
4
4
5.5
7.5
6-10
GV3-M20 /ME
4
7.5
7.5
7.5
10
11
10-16
GV3-M25 /ME 5.5
11
11
11
15
18.5
16-25
GV3-M40 /ME 11
18.5
22
22
25
33
25-40
GV3-M63 /ME 15
30
33
33
40
55
40-63
GV3-M80 /ME 22
40
45
45
55
63
56-80