OHVS series MCB
OHVS 1P OHVS 2P
OHVS 3P OHVS
Specifications
Standard Conformity
IS 8828:96 & IEC(60898:2002)
 
Type/Series
B
C
D
 
Rated Current(In)
A
6 - 40
0.5 - 63
0.5 - 63
 
Rated Voltage(ac)(Ue)
V
240/415
240/415
240/415
 
Rated Frequency(f)
Hz
50
50
50
 
Poles
 
1P.2P.3P.4P
 
2P.2P3P.4P
 
Rated Short Circuit Breaking Capacity
kA
10
10
4.5
 
Magnetic Release Setting
 
(3 - 5)In
(5-10)In
(10-20) In
 
Rated Insulation Voltage(ui)
V
660
660
660
 
Reted Impulse Voltage(Uimp)
kV
4
4
4
 
Electrical/Mechanical Endurance
(no.of operations)
less than 32A
More than 32A
 
20,000
10,000
20,000
10,000
20,000
10,000
 
Ambient Temperature
(℃)
-5 to +55
-5 to +55
-5 to +55
 
Terminal Capacity(max)
sq.mm
25
25
25
 
Vibration
g
3
3
3
 
Shock
 
40mm free fall
40mm free fall
40mm free fall
 
PRotection Class
 
 
IP - 20
 
 
Installation Position
 
 
Vertical / Horizontal
 
 
Mounting
 
 
Clip on DIN Rail (35mm × 7.5 mm)
 
 
Case & Cover
 
 
Moulded,flame retardant thermoplastic material
 
Characteristics curve
Thermal Tripping
Magnetic Tripping
 
As per
No tripping
Tripping
Time
Hold
Trip
Time
 
IS:8828:96
current
currebt
Limits
current
current
Limits
 
 
1
1
t
1
1
t
 
B Curve
1.13×1N
 
≥1h
3×1N
 
≥Y0.1s
 
 
 
1.45×1N
<1h
 
5×1N
<0.1s
 
C Cure
1.13×1N
 
≥1h
5×1N
 
≥Y0.1s
 
 
 
1.45×1N
<1h
 
10×1N
<0.1s
 
D Cure
1.13×1N
 
≥1h
10×1N
 
≥0.1s
 
 
 
1.45×1N
<1h
 
20×1N
<0.1s
 
13=2.55×1N
1s<t<60s for 1N<32A
1s<t<120s for 1N>32A
Tripping Characteristics
Based on theTripping Characteristics,MCBs are available in?‘B’、‘C’ and ‘D’ curve to suit different types of applications.
‘B’ Curve:for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits) Short circuit release is set to (3-5) In
‘C’ Curve:for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits) Short circuit release is set to (5-10) In
‘D’ Curve: for protection of electrical circuits which causes high inrush current,typically 12-15 times the thermal rated current (transformers,X-ray machines etc.)Short circuit release is set to (10-20) In
Characteristics curve
Dimensions (in mm)